PULS - CP20.241-R2 - PSU DIN Rail with Redundancy
This power supply features integrated decoupling function for 1+1 and n+1 redundancy. In addition, the CP20.241-R2 PSU power supply has an easy fuse-breaking solution 3 times the nominal current for 12ms.
Dimensions (WxHxD): 39mm x 124mm x 117mm
Mounting method: DIN rail
Operating temp. Range: -25°C to 70°C
Connection method: Screw terminals
AC Input voltage: AC 100 - 240V (-15%/+10%)
DC Input voltage: DC 110V - 150V (± 20%)
Harmonic correction: active
Power factor: 0.97
Input inrush current limitation: active
Input inrush current: 6A / 9A
External input fuse recommendation: B-6A / C-6A
Nominal voltage: 24Vdc
Adjustment range: 24V
Output current range: 10A
Output current: 10A at 24V
Output power: 240W