CL150UBCT - Boardman Transformers - CL Range

CL150UBCThttps://www.cca.co.uk/image.php?filename=cl150ubct.jpg&stockcode=CL150UBCT&category=000700490002&width=1000&height=1000

CL150UBCT - Boardman Transformers - CL Range - 150VA Control Circuit Transformer - 240/24 - Centre Tapped

Reduce your application’s voltage with Boardman Transformers. These industrial control transformers are reliable and long-lasting and will comply with the high safety standards required. Stepping down the voltage to power your control device will provide a much safer working environment for your employees. 

Boardman Transformer Range: CL 

Control Transformer:  Class 1 Isolation Transformer with Earth Screen between Primary

and Secondary

Standard: IEC / BS-EN 61558

Rating: 150VA

Voltage in: 240V

Voltage out: 24V 


Not the right transformer? 

To choose the size of transformer required for an application the total inrush VA must be calculated. This figure is then applied to the table above with the maximum allowable voltage drop taken into account. For example, for a calculated inrush of 2,100VA the appropriate transformer is as follows:

  • For 10% drop in output volts during inrush, choose 750 VA

  • For 5% drop in output volts during inrush, choose 1000 VA

Consideration must also be given to the continuous VA requirement.


If you need additional assistance on choosing the right transformer for your application, contact your local CCA branch.

GBP
Stock Code: CL150UBCT
8 In Stock for despatch
55.36£46.13 (exc VAT) per 1
£55.36 (inc VAT)
Quantity: - +

CL150UBCT - Boardman Transformers - CL Range - 150VA Control Circuit Transformer - 240/24 - Centre Tapped

Reduce your application’s voltage with Boardman Transformers. These industrial control transformers are reliable and long-lasting and will comply with the high safety standards required. Stepping down the voltage to power your control device will provide a much safer working environment for your employees. 

Boardman Transformer Range: CL 

Control Transformer:  Class 1 Isolation Transformer with Earth Screen between Primary

and Secondary

Standard: IEC / BS-EN 61558

Rating: 150VA

Voltage in: 240V

Voltage out: 24V 


Not the right transformer? 

To choose the size of transformer required for an application the total inrush VA must be calculated. This figure is then applied to the table above with the maximum allowable voltage drop taken into account. For example, for a calculated inrush of 2,100VA the appropriate transformer is as follows:

  • For 10% drop in output volts during inrush, choose 750 VA

  • For 5% drop in output volts during inrush, choose 1000 VA

Consideration must also be given to the continuous VA requirement.


If you need additional assistance on choosing the right transformer for your application, contact your local CCA branch.

Weight2.25kg
Width96mm
Height102mm
Depth76mm

Click on any of the following links to download the file.