CL200UB - Boardman Transformers - CL Range - 200VA Control Circuit Transformer - 240/24

The Boardman CL range of Industrial control transformers are a dependable and secure way to step down your voltage to power your electrical control applications. Reducing the voltage will keep your personnel safe when working on the electrical equipment. With over 60 years in manufacturing these high quality products, you can be rest-assured that Boardman transformers are reliable and made to a high quality. 

Boardman Transformer Range: CL 

Control Transformer:  Class 1 Isolation Transformer with Earth Screen between Primary

and Secondary

Standard: IEC / BS-EN 61558

Rating: 200VA

Voltage in: 240V

Voltage out: 24V 

Phase: Single Phase


Not the right transformer? 

To choose the size of transformer required for an application the total inrush VA must be calculated. This figure is then applied to the table above with the maximum allowable voltage drop taken into account. For example, for a calculated inrush of 2,100VA the appropriate transformer is as follows:

  • For 10% drop in output volts during inrush, choose 750 VA

  • For 5% drop in output volts during inrush, choose 1000 VA

Consideration must also be given to the continuous VA requirement.


If you need additional assistance on choosing the right transformer for your application, contact your local CCA branch. 

GBP
Stock Code: CL200UB
2 In Stock for despatch
64.86£54.05 (exc VAT) per 1
£64.86 (inc VAT)
Quantity: - +

CL200UB - Boardman Transformers - CL Range - 200VA Control Circuit Transformer - 240/24

The Boardman CL range of Industrial control transformers are a dependable and secure way to step down your voltage to power your electrical control applications. Reducing the voltage will keep your personnel safe when working on the electrical equipment. With over 60 years in manufacturing these high quality products, you can be rest-assured that Boardman transformers are reliable and made to a high quality. 

Boardman Transformer Range: CL 

Control Transformer:  Class 1 Isolation Transformer with Earth Screen between Primary

and Secondary

Standard: IEC / BS-EN 61558

Rating: 200VA

Voltage in: 240V

Voltage out: 24V 

Phase: Single Phase


Not the right transformer? 

To choose the size of transformer required for an application the total inrush VA must be calculated. This figure is then applied to the table above with the maximum allowable voltage drop taken into account. For example, for a calculated inrush of 2,100VA the appropriate transformer is as follows:

  • For 10% drop in output volts during inrush, choose 750 VA

  • For 5% drop in output volts during inrush, choose 1000 VA

Consideration must also be given to the continuous VA requirement.


If you need additional assistance on choosing the right transformer for your application, contact your local CCA branch. 

Weight2.8kg
Width96mm
Height102mm
Depth86mm